What is the maximum allowable resistance to ground (ohms) for a single grounding electrode without the need to add an additional grounding electrode according to the NEC?

 

 

 

ARTICLE 250 - GROUNDING AND BONDING

 

250.53 Grounding Electrode System Installation.

 

(2) Supplemental Electrode Required. 

The supplemental electrode shall be permitted to be bonded to one of the following:

(1) Rod, pipe, or plate electrode

(2) Grounding electrode conductor

(3) Grounded service-entrance conductor

(4) Nonflexible grounded service raceway

(5) Any grounded service enclosure

 

Exception: If a single rod, pipe, or plate grounding electrode has a resistance to earth of 25 ohms or less, the supplemental electrode shall not be required. 

 

 

 

NEC에 따르면 추가 접지 전극을 설치할 필요 없이 단일 접지 전극이 가질 수 있는 최대 접지 저항(옴)은 얼마입니까?

 

ARTICLE 250 - 접지 및 본딩

 

250.53 접지 전극 시스템 설치

 

(2) 추가 전극 필요

 

추가 전극은 다음 중 하나에 결합될 수 있습니다:

 

(1) 막대, 파이프 또는 플레이트 전극

(2) 접지 전극 도체

(3) 접지된 서비스 입구 도체

(4) 비유연성 접지된 서비스 레이스웨이

(5) 접지된 서비스 인클로저

 

예외:

 

단일 막대, 파이프 또는 플레이트 접지 전극의 접지 저항이 25옴 이하인 경우, 추가 전극은 필요하지 않습니다.