engine2 Fire Engine Pump Fuel Supply Maintenance NFPA 20 Standard for the Installation of Stationary Pumps for Fire Protection 2019 Edition 11.6.4* Fuel Supply Maintenance. 11.6.4.1 The fuel storage tanks shall be designed and installed so that they can be kept as full and maintained as practical at all times but never below 66 percent (two-thirds) of tank capacity. 11.6.4.2 The tanks shall be designed and installed so that they can always be .. 2024. 3. 18. The testing frequency and operational duration of fire engine pumps.(Diesel Engine) NFPA 20 Standard for the Installation of Stationary Pumps for Fire Protection(2019) 11.6* Diesel Engine Driver System Operation. 11.6.1 Weekly Run. 11.6.1.1 Engines shall be designed and installed so that they can be started no less than once a week and run for no less than 30 minutes to attain normal running temperature. 11.6.1.2 Engines shall run smoothly at rated speed, except for engines add.. 2024. 3. 10. 이전 1 다음 반응형